Product details
Liebert GXT5 3000VA 230VAC LCD, PF1.0, 2U,Extended Run Rack/Tower, Rail Kit Bundled
Technical Specifications
Model Number GXT5-3000IRT2UXL
3000 VA / 3000W
Dimensions and Weight
Dimensions (mm) Unit, D×W×H 540×430×85
Unit Weight (kg) 28.2
Input
Rated Voltatge 230 VAC
Rated Frequency 50 Hz / 60 Hz
Frequency Range 40 to 70 Hz
Power Factor ≥0.99
Input Power Cord C14 C20
Output
Nominal Voltage 200/208/220/230/240 VAC
Waveform Sine wave
Inverter Overload Capability >200% minimum 250 ms, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds;
105 to 125% for 60 seconds
>200% minimum
250 ms, 150 to 200% for
2 seconds; 105 to 150% for
55 seconds;
Efficiency in Online Mode Up to 93% Up to 94%
Active Eco Mode Up to 98%
Output Receptacles (8) EN60320/C13 (6) EN60320/C13;
(1) EN60320/C19
Internal Battery
Rated Voltage 72 Vdc
Charger Current Nominal 2.2 A; Maximum 8 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 6 x 12 V x 9.0 Ah
End Cell Voltage 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc)
Floating Voltage Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell
Battery Voltage Range 60 Vdc to 84.6 Vdc
General
Operating Temperature, °C Full power up to 40 ºC (up to 50 ºC with derating)
Storage Temperature, °C -20 to 60 ( contain batteries will be from -15 to 40 °C.)
Relative Humidity 0 to 95% non-condensing
Operating Elevation Up to 3,000 m at 25°C without derating
Audible Noise
<46 dBA max @ 3 ft. (1 m) front and
sides <43 dBA max @ 3 ft. (1 m) rear
<46 dBA max @ 3ft.
(1 m) front and
sides <45 dBA max
@ 3 ft. (1 m) rear
<48 dBA max @ 3ft. (1m) front and
sides <48 dBA max @ 3 ft. (1 m) rear
Safety CE, UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
RFI/EMI CISPR22 Class A (RFI)/ FCC Part 15 (Class A)
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B